One (1) Harrison Hydraulic Driven Generator model number 30.0MPC-16D rated at 30000 watts, 125/250 amps, 120/240VAC, 60Hz, 1-phase.  The system shall be designed and assembled by a company with no less than 10 years experience in the manufacture of hydraulic driven generators.  The system shall be tested at the full nameplate load prior to shipping and be accompanied with the test report.  The test report will document the generator’s performance at various loads from no load to full load to ensure reliable power delivery at those loads. 

The motor/generator shall be placed in a frame which affords protection to the components and provides a unitized mounting module containing the motor/generator, reservoir, oil cooler, filtration, manifold containing a cross port check valve and relief valve.  The generator shall be a continuous duty, industrial type with a heavy-duty bearing and of brushless design to ensure low maintenance.  No brushes or slip rings will be allowed.  The reservoir shall include an oil level sight gauge, oil temperature gauge, fill cap, oil filter, low fluid level sensor, high temperature sensor and a venturi boost unit to provide positive pressure to the pump suction port.  The generator and motor shall be close coupled and aligned using a single bearing alternator design.  No two (2) bearing generators shall be permitted.

The system must be capable of producing the full nameplate power when driven from the vehicle PTO from idle to maximum engine speed.  The generator system must be able to operate on either a Constant Engaged PTO or a Hot Shift PTO.  Determination as to which PTO to use will be made by the Fire Department.  The generator must be able to be used while vehicle is either stationary or in motion.

The hydraulic motor and pump shall be of axial piston design to provide low internal leakage and a high degree of frequency stability.  No gear pumps or motors will be used.  The pump shall match the system with the proper orifice, pressure compensator, and load sense settings to provide stable output regardless of engine rpm or electrical load demands.

The system shall be capable of normal operations using a commonly available ATF fluid, such as GM Dextron II, III, or equivalent.  All fluid service points shall be in close proximity to the reservoir for ease of scheduled maintenance.

When properly installed, the system shall be warranted for a period of not less than two (2) years or 2000 hours, whichever should come first.

A Quadra meter containing the volt, amp, and frequency is to be provided and installed in a location, which is away from the weather and water over spray.  If the meter is to be installed in the elements then a weatherproof digital meter is to be used.

Harrison Hydra-Gen 30.0 MPC – 16B/2A Specifications  

DIMENSIONS:  Reservoirs are shipped attached, but can be remote mounted.  (Tray unit dimensions and weights are without the reservoir.)

Tray Unit

Reservoir

Length

24”

22.5”

Width

35”

6”

Height

20”

18.5”

Weight

560 lbs

24 lbs

Max  KW

30.0kW

Amps @ 120V

250

Amps @ 240V

125

HP Required

64

Torque Required

211

Max System PSI

5400

ALTERNATOR DETAIL

Design Brushless revolving field, four pole, 1800 rpm for 60 hertz operation.
Rating See nameplate for individual rating.
Regulation +/-  1% Voltage regulation from nameplate rating.
Waveform Harmonic distortion is limited to just 4 %
Insulation Class H, 200° C, Slot Insulation, Varnish. Additional Marine Coating.
Power Factor 1.0 (unity) for single – phase units, 0.8 for three phase units.

HYDRAULIC SYSTEM

Type of oil:  Use only premium hydraulic fluid with anti wear, anti foam, and anti rust additives. Optimum operating viscosity is 80-170 SSU. Viscosity should never exceed 4,600 SSU at the coldest startup temperature, and never less than 60 SSU at 180 degrees F.
Capacity: The reservoir should contain a minimum of 7.5 gallons (U.S.) of oil.

HYDRAULIC PUMP INFORMATION: (80cc)

  Minimum/ Maximum Shaft Speed
(Note: for speeds above 3000 rpm consult Harrison Hydra-Gen factory)
1000 RPM/3000 RPM
  Displacement 80 CC
  Max. Temperature 204° F
  Min. Temperature -4° F
  Weight of Pump 78 lbs
  Max. Torque 295 ft. lbs
  Pump shaft    SAE “C” Spline or Keyed
  Rotation CW or CCW
  Max. Pressure   5200 psi
  Max. Vacuum  10.0 in, hg.