Harrison Hydra-Gen Model 5.0 MSV-16R Specifications

Hydraulic Driven A/C Electric System

The generator system shall be a Harrison model 5.0MSV-161R, rated at 5.0 kilowatts, 120/240 VAC, single Phase, 60 Hertz, or approved equal.  The system shall be designed and assembled by a company with no less than 10 years experience in the manufacture of hydraulic driven systems.

The motor/generator shall be placed in a tray frame assembly, which affords protection to the components and provides a unitized mounting module containing motor/generator, reservoir, oil cooler, filtration system and a priority flow control. The tray frame assembly is to be painted with a powder coated epoxy paint and the top cover shall be slip resistant aluminum diamond tread plate conforming to NFPA 1901 Section 17-7.3.

The generator shall be a brushless revolving field, two poles, 3600 RPM for 60-hertz operation commercial type with heavy-duty bearings designed to ensure low maintenance.   No brushes or slip rings will be allowed. The generator and hydraulic motor shall be coupled and aligned to generator shaft.   

The system must be capable of producing the rated full-load power at a 120°F air inlet temperature.

The pump shall match the system with the proper orifice, pressure compensator, and load sense settings to provide stable output regardless of engine rpm or electrical load demands.

The reservoir shall include an oil level indicator, filler/breather cap, in tank filter, and a boost unit to provide a positive pressure to the pump suction port. 

The hydraulic motor shall be a balanced plate gear motor, .61 cu/in displacement having SAE side ports, external case drain and incorporate an anticavitation check valve and a system safety relief in the rear cover.

Cooling of the hydraulic system must include an air over hydraulic heat exchanger with a temperature regulated 12 VDC fan. No direct driven fans will be accepted.

The system shall be capable of normal operations using a commonly available hydraulic   fluid, such as GM DEXTRON II, III, or equivalent.  All fluid service points shall be in close proximity for ease of scheduled maintenance.

When properly installed, the system shall be warranted by the manufacturer for a period of not less than two years or two thousand hours, which ever should come first.

GENERATOR DETAILS:

The MSV series is a self-exciting brushless generator, designed to operate with single-phase loads at or near a power factor of 1.0. The auxiliary winding, in conjunction with the excitation capacitor, provides excitation by inducing current in the rotor (field) windings, which is rectified to produce a direct current field. The main stator winding is designed for series/parallel connection to give a dual voltage output and no voltage adjustment is possible.

Design Brushless revolving field, two pole, 3600 rpm for 60-hertz operation
Volts 240 / 120 VAC
Phase Single
Amps 25/50
Power Factor 1.0
Insulation Class F

HYDRAULIC SYSTEM:

DRIVE MOTOR

Type Pressure Balanced gear motor Displacement 10 CC .61 CU/IN
Max Pressure 3200 PSI
Case Drain External
Valve Option Crossover relief and overrunning check valve
Rotation Counterclockwise

RESERVOIR

Dimensions 8.0” H x 5.0” W x 29.0” D
Capacity 5 U.S. Gallons (by size)

OIL TYPE

Use only premium hydraulic fluid with anti wear, anti foam, and anti rust additives.
Optimum operating viscosity is 80-170 SUS.

PUMP REQUIREMENTS

The generator can operate using a

Flow 10.5 GPM to 11.0 GPM
Pressure 3000 PSI

 